Standard case DIN rail mounting TS35 Floor space 22.5x75mm (WxH) Mounting height 110mm Features - Monitoring of battery voltage 12V, 24V, 48V or 60V
- Current demand max. 14mA (24mA 12V type) with activated relay
- Output 1 relay SPDT 250V AC / 2A
- Alarm function undervoltage / overvoltage
- Switching hysteresis adjustable 2 ... 16%
- Time delay in 2 ranges adjustable (1 ... 60s or 5 ... 300s)
- Measuring voltage = supply voltage
- 2 LED´s for setpoint and power
The BW 500 was designed for monitoring of battery voltages. Undervoltage or overvoltage can be selected. - Undervoltage : The relay switches off, if the voltage falls under the limit value and if the delay time ran off.
If the voltage exceeds the limit value+hysteresis, the relay will be activated - Overvoltage : The relay switches on, if the voltage exceeds the limit value and if the delay time ran off.
If the voltage falls under the limit value-hysteresis, the relay will be deactivated.
Device specification |
Battery voltage |
Options |
|